BV-90 series

Technical Data

National standard: GB/T5023.3-2008

Cable Structure

Application

This series of products is suitable for wiring of electrical control lines inside equipment, and also for wiring inside buildings.

image.png

Insulation layer: material-high-quality PVC/C; 

Conductor: material-oxygen-free copper.


The number of conductor cores is 1 core, which should meet the requirements of GB/T 3956, the first type for solid conductors and the second type for stranded conductors!


Conductor Nominal Cross Section mm2Conductor typeInsulation Thickness Specified Value mmAverage outer diameter upper limit mmMinimum insulation resistance at 70°C MΩ·km
1.510.7 3.3 0.011
1.520.7 3.4 0.010
2.510.8 3.9 0.010
2.520.8 4.2 0.009
410.8 4.4 0.0085
420.8 4.8 0.0077
610.8 4.9 0.0070
620.8 5.4 0.0065
1011.0 6.4 0.0070
1021.0 6.8 0.0065
1621.0 8.0 0.0050
2521.2 9.8 0.0050
3521.2 11.0 0.0040
5021.4 13.0 0.0045
7021.4 15.0 0.0035
9521.6 17.0 0.0035
12021.6 19.0 0.0032
15021.8 21.0 0.0032
18522.0 23.5 0.0032
24022.2 26.5 0.0032
30022.4 29.5 0.0030
40022.6 33.5 0.0028


Product StandardsProduct numberProduct SpecificationsNumber of conductorsConductor diameterAverage thickness of core wireInsulation outer diameterMaximum conductor resistance at 20°CMinimum insulation resistance at 90°C
NmmmmmmΩ/kmMΩ.km
GB/T5023.3-2008(300/500V)60227 IEC 07(BV-90)1×0.510.800 0.65 2.10 36.00 0.015 
GB/T5023.3-2008(300/500V)60227 IEC 07(BV-90)1×0.7510.980 0.64 2.25 24.50 0.013 
GB/T5023.3-2008(300/500V)60227 IEC 07(BV-90)1×1.011.130 0.64 2.40 18.10 0.012 
GB/T5023.3-2008(300/500V)60227 IEC 07(BV-90)1×1.511.380 0.76 2.90 12.10 0.011 
GB/T5023.3-2008(300/500V)60227 IEC 07(BV-90)1×2.511.780 0.86 3.50 7.41 0.009