BVR series

Technical Data

National Standard: JB/T8734.2-2012

Cable Structure

Application

This series of products is suitable for internal wiring of buildings, and can also be used for lightning protection equipment to introduce underground wires.

image.png

Insulation layer: material-high-quality PVC/C; 

Conductor: material-oxygen-free copper.


image.png


Nominal cross-sectional area mm2Minimum number of single wires in stranded conductorsInsulation Thickness Specified Value mmAverage outer diameter upper limit mmMaximum conductor resistance at 20°C Ω/kmMinimum insulation resistance at 70°C MΩ·km
copper coreTinned copper core
0.7570.72.924.524.80.013
1.070.73.118.118.20.012
1.570.73.412.112.20.011
2.5190.84.17.417.560.011
4190.84.84.614.700.009
6190.85.33.083.110.0084
10491.07.31.831.840.0072
16491.08.61.151.160.0062
25981.210.20.7270.7340.0058
351331.211.70.5240.5290.0052
501331.413.90.3870.3910.0051
701891.416.00.2680.2700.0045
952591.618.20.1930.1950.0044
1202591.619.80.1530.1540.0040
1503361.822.20.1240.1260.0040
1854272.024.60.09910.1000.0040


Product StandardsProduct numberProduct SpecificationsNumber of conductorsConductor diameterAverage thickness of core wireInsulation outer diameterMaximum conductor resistance at 20°CMinimum insulation resistance at 70°C
NmmmmmmΩ/kmMΩ.km
JB/T8734.2-2012(450/750V)BVR1×2.5190.410 0.87 3.80 7.41 0.011
JB/T8734.2-2012(450/750V)BVR1×4.0190.520 0.87 4.35 4.61 0.009
JB/T8734.2-2012(450/750V)BVR1×6.0190.630 0.86 4.90 3.08 0.0084
JB/T8734.2-2012(450/750V)BVR1×10.0490.510 1.09 6.30 1.83 0.0072